Coggan, Robert Walter (2010) High impedance earth fault modelling. [USQ Project]
|
PDF
Coggan_2010.pdf Download (1MB) |
Abstract
[Abstract]: Single Wire Earth Return (S.W.E.R) Distribution networks were installed by Electrical Distribution entities to distribute power to customers who are remote from Zone
Substations and have a low energy demand. As is common with typical distribution systems, S.W.E.R. systems are being subjected to an array of appliances with higher energy demands than were ever anticipated. An increase in load without an increase in the available fault current highlights the benefits of non traditional fault detection
techniques. Detection of faults historically relied on the use of fundamental power system signals to distinguish between normal operation and fault conditions. Recent
introduction of microprocessor based protection relays allows monitoring of low level signals generated by power system faults to increase the protection coverage. The
project has deconstructed a typical SWER power system and validated models for each power system component. COMTRADE files have been produced that can be replayed to protection relays attempting to detect arching and high impedance faults.
Statistics for this ePrint Item |
Item Type: | USQ Project |
---|---|
Refereed: | No |
Item Status: | Live Archive |
Faculty/School / Institute/Centre: | Historic - Faculty of Engineering and Surveying - Department of Electrical, Electronic and Computer Engineering (Up to 30 Jun 2013) |
Supervisors: | Ahfock, Tony |
Date Deposited: | 22 Feb 2011 04:22 |
Last Modified: | 03 Jul 2013 00:30 |
Uncontrolled Keywords: | electricity; single wire earth return (SWER); current fault detection |
Fields of Research (2008): | 09 Engineering > 0906 Electrical and Electronic Engineering > 090601 Circuits and Systems |
Fields of Research (2020): | 40 ENGINEERING > 4008 Electrical engineering > 400801 Circuits and systems |
URI: | https://sear.unisq.edu.au/id/eprint/18416 |